Toshiba Klima Arıza Kodları

Güncel Toshiba Arıza Kodları…

Fault code = 0C
Fault = ROOM TEMP. SENSOR (TA)
Out of place, break,short-circuit.
Operation continuing = 1. Check the indoor temp. sensor. 2. Check the indoor PC board

Fault code = 0d
Fault = INDOOR HEAT-EXCHANGER SENSOR (TC).
Out of place, break, short-circuit.
Operation continuing = 1. Check the indoor

heat-exchanger sensor. 2. Check the indoor PC board

Fault code = 04
Fault = RETURN SIGNAL NOT COMING TO INDOOR.
1) Wrong wiring in connecting cable (serial signal).
Operation continuing
1. If outdoor unit does not work at all.
(1) Check the connecting cable correct wrong wiring.
(2) Check the outdoor PC board.
2. If operates normally.
Between indoor terminal plates 2 and 3, return signal is:
Available: Check the indoor PC board.
Not available: Check the outdoor PC board.

Fault code = 08
Fault = 4-WAY VALVE SYSTEM
1) Indoor heat-exchanger temperature rises, after starting cooling operation.
2) Indoor heat-exchanger temperature drops after starting heating operation
Operation continuing
1. Check the 4-way valve.
2. Check the 2-way valve and check valve.
3. Fault with indoor heat exchanger sensor.
4. Check the indoor PC board.

Fault code = 09
Fault = OTHER CYCLE SYSTEM
1) Indoor heat exchange temperature does not change after starting cooling/heating operation.
2) When transmitting instruction for stopping compressor by freeze preventing control.
Operation continuing
1. Compressor case thermostat, IOL, OL operation. (contactor OFF, compressor stops: AH8 Models) (contactor ON, compressor stops: AH Models)
2. Indoor heat-exchange sensor out of place.
3. Check the indoor PC board.
4. Check that service valves are OPEN.
Outdoor unit stops (indoor fan L)
1. Check the charged amount of refrigerant gas.
(Gas shortage ® gas supplement, check for gas leaks)
2. Indoor fan locked.

Fault code = 18
Fault = DEFROST SENSOR (TE)
Out of place, break, shortcircuit.
Full stop
1. Check the defrosting sensor.
2. Check the outdoor PC board

Fault code = 19
Fault = OUTDOOR HEAT-EXCHANGER SENSOR (TL)
Out of place, break, short-circuit.
Full stop
1. Check the outdoor heat-exchanger sensor.
2. Check the outdoor PC board

Fault code = 21
Fault = HIGH PRESSURE SWITCH
High pressure switch does not reset. (5 sec in cooling 30 sec in heating)
Full stop
1. Check the high pressure switch.
2. Check the outdoor PC board

Fault code = 1C
Fault = OTHER ABNORMALITY OF OUTDOOR UNIT
Compressor does not operate. Start once, but soon after stop by OCR
Full stop
1. Check the compressor.
2. Check the wiring of compressor. (lack of phase, short circuit)
3. Check the voltage.
4. Check the outdoor PC board.

Fault code = 99
Fault = WRONG WIRING OF REMOTE CONTROL UNIT
Indoor unit does not operate at all.
Full stop
1. Check the wiring between remote control unit and indoor unit.
2. Check the indoor unit PC board.

Fault code = 0b
Fault = FLOAT SWITCH
Outdoor unit stops
1. Fault in drain pump.
2. Drain pipe clogged.
3. Check for indoor PC board

 

Toshiba Fault Codes with RealTime Fault Extensions

Fault Code LTX/FDP3 Fault Description

 

C05 17157 Sending error in TCC-LINK central control device

C06 17158 Receiving error in TCC-LINK central control device

C12 17164 Batch alarm of general-purpose equipment control interface

E01 17665 Communication error between indoor and remote controller (Detected at remote controller side)

E02 17666 Sending error of remote controller

E03 17667 Communication error between indoor and remote controller (Detected at indoor side)

E04 17668 Communication circuit error between indoor and outdoor (Detected at indoor side)

E06 17670 Decrease of No. of indoor units

E07 17671 Communication circuit error between indoor/outdoor (Detected at outdoor side)

E08 17672 Duplicated indoor addresses

E09 17673 Duplicated master remote controllers

E10 17674 Communication error between indoor P.C.board

E12 17676 Automatic address start error

E15 17679 No indoor automatic address

E16 17680 Capacity over/No. of connected indoor units

E18 17682 Communication error between indoor header and follower units

E19 17683 Outdoor header units quantity error

E20 17684 Other line connected during automatic address

E23 17687 Sending error in communication between outdoor units

E25 17689 Duplicated follower outdoor address

E26 17690 Decrease of No. of connected outdoor units

E28 17692 Follower outdoor unit error

E31 17695 IPDU communication error

F01 17921 Indoor TCJ sensor error

F02 17922 Indoor TC2 sensor error

F03 17923 Indoor TC1 sensor error

F04 17924 TD1 sensor error

F05 17925 TD2 sensor error

F06 17926 TE1 sensor error

F07 17927 TL sensor error

F08 17928 TO sensor error

F10 17930 Indoor TA sensor error

F12 17932 TS1 sensor error

F13 17933 TH sensor error

F15 17935 Outdoor temp. sensor misconnection (TE1,TL)

F16 17936 Outdoor pressure sensor misconnection (Pd,Ps)

F23 17943 Ps sensor error

F24 17944 Pd sensor error

F29 17949 Indoor other error

F31 17951 Outdoor EEPROM error

H01 18433 Compressor break down

H02 18434 Magnet switch error / Overcurrent relay operation / Compressor error (lock)

H03 18435 Current detection circuit error

H04 18436 Comp-1 case thermo operation

H06 18438 Low pressure protective operation

H07 18439 Low oil level protection

H08 18440 Oil level temp. sensor error

H14 18446 Comp-2 case thermo operation

H16 18448 Oil level detection circuit error / Magnet switch error / Overcurrent relay error

L03 19459 Duplicated indoor header units

L04 19460 Duplicated outdoor line address

L05 19461 Duplicated indoor units with priority (Displayed in indoor unit with priority)

L06 19462 Duplicated indoor units with priority (Displayed in unit other than indoor unit with priority)

L07 19463 Group line in individual indoor unit

L08 19464 Indoor group/Address unset

L09 19465 Indoor capacity unset

L10 19466 Outdoor capacity unset

L20 19476 Duplicated central control addresses

L28 19484 Maximum number of outdoor units exceeded

L29 19485 No. of IPDU error

L30 19486 Auxiliary interlock in indoor unit

L31 19487 IC error

P01 20481 Indoor fan motor error

P03 20483 Discharge temp. TD1 error

P04 20484 High-pressure switch detection error

P05 20485 Phase-missing detection / Phase order error

P07 20487 Heat sink overheat error

P10 20490 Indoor overflow error

P12 20492 Indoor fan motor error

P13 20493 Outdoor liquid back detection error

P15 20495 Gas leak detection

P17 20497 Discharge temp. TD2 error

P19 20499 4-way valve inverse error

P20 20500 High-pressure inverse error

P22 20502 Outdoor fan IPDU error

P26 20506 G-Tr short circuit protection error

P29 20509 Comp position detection circuit error

P31 20511 Follower indoor unit error (Group error)

S00 21248 Intelligent Server Communication error

S01 21249 Communication error between indoor unit and BMS

S02 21250 TCS-NET Relay Interface Communication error

S03 21251 Group terminal unit error

S04 21252 BMS-IFWH Communication error

S05 21253 BMS-IOKIT Communication error

S06 21254 Communication error

S07 21255 Communication error

S08 21256 Communication error

S09 21257 Communication error

V00 22016 VCI Zero Value – No Unit Present

V80 22096 VCI waiting for unit data

V81 22097 VCI poll failure – no response after 8 retries

V82 22098 VCI poll failure – no response within timeout period

V83 22099 VCI Unit Comms error generated by A/C interface

V84 22100 VCI Unit missing error generated by A/C interface

V85 22101 VCI Fault : zero fault code recieved

V86 22102 VCI Fault : zero setpoint readback value

V87 22103 VCI Fault : zero temperature value

V88 22104 VCI Fault : null temperature value

V89 22105 VCI Fault : unknown error

  • Site Yorum
  • Facebook Yorum

14 adet yorum var.

  1. ismet dedi ki:

    Usta toshiba inverter ras 16 modelinin ariza kodlarini bulamiyorum burada ise ingilizce yaziyor yardimci olursaniz sevinirim tesekurler.

  2. ali dedi ki:

    toshıba vrf p 22 arızası veriyor açık fan ıbdu hatası diyor açılımı nedir acaba

  3. Galip gümüş dedi ki:

    Ali bey P22 hatası dış ünite fan hatasıdır.

  4. Suat dedi ki:

    p22 hatasını biz de sıklıkla alıyoruz;
    klimaların dış ünite sigortaları gevşediğinde de oluyor
    sigorta kablo bağlantı vidalarını sıktığımızda düzeliyor.
    bir anlam veremiyorum neden olabilir.

  5. ali dedi ki:

    Toshiba ras 18:duvar tipi split klimanin dis unite kart arizaliydi yapildi taktik simdi sogutmada aciyoruz direk isitmaya geciyor 3 yollu vana mi arizali

  6. fırat efe dedi ki:

    mitsubishi inverter klima p26 ne arızası olabilir

  7. Ahmet CENGİZ dedi ki:

    merhabalar toshiba kaset tipi H2 arızası nedir komprosör kilit hatası diyor yardımcı olursanız sevinirim

  8. ahmet dedi ki:

    merhaba p07 hatası alıyoruz mağazada çözüm nedir

  9. ALi dedi ki:

    E26 arızası var arızanın açılımının ne olduğu ve sorunu gidermek için yapmamız gereken nedir? Yardımlarınız için teşekkürler

  10. ercan dedi ki:

    E04 kodu mevcut . ne yapmamız gerekir.