York Klima Arıza Kodları

Güncel York Klima Arıza Kodları…

Temperature Sensor Resistance Readings

Temperature = 0C
K Ohms = 35K

Temperature = 10C
K Ohms = 20K

Temperature = 20C
K Ohms = 13K

Temperature = 30C
K Ohms = 8K

Fault Codes for RAHC, YKHC & YUHC Models

Indoor lights

Operation = Flash
Timer = Flash
Defrost = Flash
Faults = Outdoor Problem

Operation =
Timer =
Defrost = Flash
Faults = ID Air Sensor Fail

Operation = Flash
Timer =
Defrost =
Faults = ID Pipe Sensor Fail

Operation =
Timer =
Defrost = Flash
Faults = OD Pipe Sensor Fail

Operation = Flash
Timer = Flash
Defrost =
Faults = PCB Fail

Outdoor LEDS 3ph models only

LED 1 = Flash
LED 2 = Off
LED 3 = Off
Faults = Phase Error

LED 1 = Flash
LED 2 = Flash
LED 3 = Off
Faults = Pressure Switch

LED 1 = Off
LED 2 = Off
LED 3 = Flash
Faults = Overcurrent

LED 1 = Off
LED 2 = Flash
LED 3 = Flash
Faults = OD Pipe Sensor

LED 1 = Off
LED 2 = Flash
LED 3 = Off
Faults = OD Air Sensor

LED 1 = Flash
LED 2 = Flash
LED 3 = Flash
Faults = Hi Temp Protection

HVHC Inverter Fault Codes

Indoor Display = E0
ID PCB Fail
Outdoor LCDs
1 = On
2 Red = Off
3 Green = Off
4 Yellow = Off
Connected to Power

Indoor Display = E1
Comms Fail
Outdoor LCDs
1 = Off
2 Red = Off
3 Green = Off
4 Yellow = Off
Power or OD PCB Fail

Indoor Display = E3
Power Abnormal
Outdoor LCDs
1 = On
2 Red = On
3 Green = Off
4 Yellow = Off
Comms Fail

Indoor Display = E4
OD Sensor Fail
Outdoor LCDs
1 = On
2 Red = Off
3 Green = Off
4 Yellow = On
Compressor Overcurrent

Indoor Display = E5
ID Sensor Fail
Outdoor LCDs
1 = On
2 Red = Off
3 Green = Flash
4 Yellow = Flash
OD Air Sensor Fail E5

Indoor Display = E6
Inverter Module
Outdoor LCDs
1 = On
2 Red = Flash
3 Green = Off
4 Yellow = Flash
OD Pipe Sensor Fail E5

Indoor Display = PO
IPM Protection
Outdoor LCDs
1 = On
2 Red = On
3 Green = Flash
4 Yellow = On
OD Power Supply P1

Indoor Display = P1
OD Power Supply
Outdoor LCDs
1 = On
2 Red = Off
3 Green = On
4 Yellow = Off
IPM Protection P0

Indoor Display = P2
Compressor Hi Temp
Outdoor LCDs
1 = On
2 Red = Off
3 Green = On
4 Yellow = On
Compressor Temp P2

Indoor Display = P3
Outdoor Low Temp
Outdoor LCDs
1 = On
2 Red = On
3 Green = Off
4 Yellow = Off
Comms E1

Indoor Display = P4
Inverter/Compressor Fail
Outdoor LCDs
1 = On
2 Red = On
3 Green = Flash
4 Yellow = Flash
Inv / Comp Fail P4

Model SM-YJCC-YJHC

Items to be checked first
1. Is the voltage of the power correct? The input voltage shall be rating voltage 10%. The air conditioner may not operate properly if the voltage is out of this range.
2. Is the link cable connecting the indoor unit and the outdoor unit linked properly? Please refer to the “wiring diagram” Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables.
3. When a problem occurs due to the contents illustrated in the table below, it is symptomnot related to themalfunction of the air conditioner.

Operation of air conditioner = In COOL operation mode, the compressor does not operate at a room temperature higher than the setting temperature that the indoor fan should operate.In a HEAT operation mode, the compressor does not operate at a room temperature lower than the setting temperature that indoor fan should operate.

Explanation = It happens after a delay of 3 minutes when the compressor is reoperated. The same phenomenon occurs when a power is on.As a phenomenon that the compressor is reoperated after adelay of 3 minutes, the indoor fan is adjusted automatically withreference to a temperature of the air blow.

Operation of air conditioner = Fan speed setting is not allowed in AUTO or DRY mode

Explanation = The speed of the indoor fan is set to low in DRY mode.Fan speed of 3 steps is selected automatically in AUTO mode.

Operation of air conditioner = Compressor stops operation intermittently in DRY mode.

Explanation = Compressor operation is automatically controlled in DRY modedepending on the room temperature and humidity.

Operation of air conditioner = Compressor of the outdoor unit is operating although it is turned off in HEAT mode.

Explanation = When the unit is turned off while de-ice is activated, thecompressor continues operation for up to 10 minutes(maximum)until the deice is completed.

Operation of air conditioner = Timer indicator lamp lights up and the air conditioner doesnot operate.

Explanation = Timer is being activated and the unit is in ready mode.The unit operates normally if the timer operation is cancelled

Operation of air conditioner = The compressor and indoor fan stop intermittently in HEATmode.

Explanation = The compressor and indoor fan stop intermittently if room temperature exceeds a setting temperature in order to protectthe compressor from overheated air in HEAT mode

Operation of air conditioner = Indoor fan and outdoor fan stop intermittently in HEAT mode.

Explanation = The compressor operates in a reverse cycle to remove exteriorice in HEAT mode, and indoor fan and outdoor fan do not operate intermittently for within 20% of the total heat operation

Operation of air conditioner = The compressor stops intermittently in COOL mode or DRYmode, and fan speed of the indoor unit decreases

Explanation = The compressor stops intermittently or the fan speed of the indoor unit decreases to prevent inside/outside air frozendepending on the inside/outside air temperature.

SELF DIAGNOSIS FUNCTION
Our company provides the end-users with thoughtful services by installing various diagnostic systems to indicate the following irregular performances

Checkcode = FAULT F6
Diagnosis of malfunction = PG motor faults

Checkcode = FAULT F7
Diagnosis of malfunction = Indoor TEMP sensor faults

Checkcode = FAULT F8
Diagnosisofmalfunction = Indoor coil pipe TEMP sensor faults

Checkcode = FAULT F9
Diagnosisofmalfunction = Outdoor coil pipe TEMP sensor faults